- There are no more items in your cart
- Shipping Calculated at checkout
-
Sub-Total (inc. VAT)
£0.00
Preformed self-adhesive intumescent plates to reinstate the fire resistance performance of flexible wall constructions for up to 120 minutes when punctured with plastic wall boxes. Used where walls have been provided with apertures for the penetration of conduits and cables into socket boxes, on one or both sides of the wall.
- 2022 certification upgrade adds UK style socket boxes rated to EI 120 in drywalls and socket boxes can in addition, be fixed to timber noggins
- Intumescent electrical socket box plates - expands in the heat of a fire, filling holes and gaps to prevent passage of fire
- Up to 120 minutes of both integrity and insulation resistance
- Quick and easy to install - Wall boxes can be fitted back to back
- For flexible walls with a minimum thickness of 75 mm
- Can be used on insulated and uninsulated walls
- Tested with a wide range of cables and conduits interconnected between boxes, and empty conduits between boxes for future cable transits
- See Fire Classification below for FR Graphite Plates made to special order for specific socket boxes
Protecta FR Graphite Plate, part of the Protecta Firestopping range, is a preformed self-adhesive intumescent plate used to reinstate the fire resistance performance of flexible wall constructions for up to 120 minutes when punctured with plastic wall boxes. It is used where the walls have been provided with apertures for the penetration of conduits and cables into socket boxes, on one or both sides of the wall.
The graphite plate immediately reacts to fire through the heat and automatically expands and fills up the box, preventing fire from passing through. Fitting Protecta FR Graphite Plate will reinstate the fire resistance performance of flexible wall constructions for up to 120 minutes, also preventing the passage of fire through the electrical conduits between socket boxes.
Features & Benefits
- Intumescent electrical socket box plates
- Expands in the heat of a fire, filling holes and gaps to prevent passage of fire
- Reinstate the fire resistance performance of flexible wall constructions
- Up to 120 minutes of both integrity and insulation resistance
- Wall boxes can be fitted back to back
- Quick and easy to install
- For flexible walls with a minimum thickness of 75 mm
- Can be used on insulated and uninsulated walls
- Tested with a wide range of cables and conduits interconnected between boxes
- Tested with empty conduits between boxes for future cable transits
Ordering References
Reference | Product Name | Size | Colour | Pack Quantity |
---|---|---|---|---|
P210 | Protecta FR Graphite Plate | 45x45mm Square | Grey | Box of 10 |
P211 | Protecta FR Graphite Plate | 59mm Diameter Circle | Grey | Box of 10 |
See Fire Classification below for FR Graphite Plates made to special order for specific socket boxes - contact our sales team on 0113 2455450 or [email protected] to discuss your requirements.
Technical Data
Technical Approval | ETAG 026-2 |
Fire Test - EN13501-2 | EI 30 - 120 |
Durability - ETAG 026-2 | Z 2 intended for use in internal conditions with humidity classes other than Z 1 , excluding temperatures below 0°C |
Conditioning procedure | EN 13238:2010 |
Expansion ratio | 17:1 |
Expansion pressure | 65.4 N |
Colour | Light Grey with silver flecks |
Texture | Textured surface |
Finish | Matt finish on one side, other side satin finish |
Thickness | Approximately 3.8mm |
Weight per unit area / length | 5.1 Kgm² |
Density | 1,409 Kgm³ |
Optimum expansion time | 2 minutes |
Optimum expansion temp. | 550°C |
Usage | Supplied ready to fit, normally one plate is required per electrical socket box |
Storage | Store in temperatures between 5°C and 30°C |
Life | Under normal conditions; 50 years + |
Application Instructions
Minimum separations and limitations: Socket boxes can be fitted back to back or side by side – one fitted to each face. Minimum separation between socket boxes on one side of the wall should be at least 30 mm.
Supporting constructions: Flexible walls must have a minimum thickness of 75 mm and comprise steel studs or timber studs*** lined on both faces with minimum 1 layer of 12.5 mm thick boards. The supporting construction must be classified in accordance with EN 13501-2 for the required fire resistance period.
***Timber studs: no part of the penetration seal may be closer than 100 mm to a stud, and minimum 100 mm of insulation of class A1 or A2 according to EN 13501-1 must be provided within the cavity between the penetration seal and the stud.
Installation
- Wall boxes should be installed according to the Manufacturer’s Instructions.
- The aperture around the wall box should be as tightly fitting as possible and any gaps filled with plaster filler.
- Before installing Protecta FR Graphite Plate ensure that the surfaces are clean and sound, free from dirt, grease and other contamination.
- Remove the backing paper from the back of the pad.
- Fit into place inside at the base of the socket box.
- The pad must not obstruct cable entry.
Test Standards
This Technical Data Sheet is based on the product’s European Technical Assessment, issued in accordance with regulation (EU) No 305/2011, on the basis of EAD 350454-00-1104, September 2017.
Fire Classification
Socket Box | Graphite Plate | Class |
---|---|---|
FLEXIBLE WALL CONSTRUCTIONS ≥ 75MM | ||
ELKO 3012 S57/100 standard box | Square 45 x 45mm | E 60, EI 45 |
UK standard socket boxes up to 145mm wide x 85mm high x 35mm deep | Square 110 x 60mm | EI 30 |
FLEXIBLE WALL CONSTRUCTIONS ≥ 100MM | ||
ABB AU60.1 2TKA001744G1/122008 connection box | Square 45 x 45mm | EI 60 |
ELKO 45/Stud 6-conduits standard box | Circular Ø 59mm | EI 60 |
ELKO 3011 connection box | 2no. plates 55 x 45mm | EI 60 |
ELKO 3012 S57/100 standard box | Square 45 x 45mm | EI 60 |
ELKO 4038 connection box | Square 30 x 30mm | EI 90 |
ELKO 4040 connection box | Square 45 x 45mm | EI 60 |
ELKO 4045 connection box | Square 45 x 60mm | EI 60 |
ELKO 4202 connection box (1) | Square 45 x 45mm | EI 60 |
ELKO 4206 connection box (1) | Square 45 x 45mm | EI 60 |
ELKO 4545 connection box | 8no. plates 20 x 35mm | EI 45 |
ELKO 5228 connection box (2) | Circular Ø 59mm | EI 60 |
FUGA Forfradåse 1M | 4no. plates 25 x 15 mm and 1no. 25 x 7 mm | EI 120 |
FUGA Air Forfradåse 1M | 4no. plates 25 x 15 mm and 1no. 20 x 20 mm | EI 90 |
RUTAB 3 connection/junction box | Special shape Ø 65mm | E 120, EI 90 |
RUTAB 8 connection/junction box | Square 57 x 74mm | EI 90 |
SCHNEIDER Electric 55/94 2-conduits connection box | 2no. plates 55 x 45mm | EI 60 |
SCHNEIDER Electric 60/46 connection box | 5no. plates 20 x 50mm | E 90, EI 45 |
SCHNEIDER Electric IMT 36006 connection box | Square 45 x 45mm | EI 60 |
SCHNEIDER Electric IMT 36016 connection box | Square 45 x 45mm | EI 60 |
SCHNEIDER Electric IMT 36029 connection box | Square 45 x 60mm | EI 60 |
SCHNEIDER Electric IMT 36030 connection box | 8no. plates 20 x 35mm | EI 30 |
SCHNEIDER Electric IMT 36190 connection box | Square 30 x 30mm | EI 120 |
SCHNEIDER Electric IMT 36192 connection box | Square 45 x 45mm | EI 60 |
SCHNEIDER Electric IMT 36193 connection box | Square 45 x 45mm | EI 45 |
SCHNEIDER Electric IMT 36200 connection box | Square 45 x 45mm | EI 60 |
SCHNEIDER Electric IMT 36205 connection box | 2no. plates 55 x 45mm | EI 60 |
SCHNEIDER Electric IMT 36256 TED A26 connection box | Square 45 x 45mm | EI 90 |
SCHNEIDER Electric IMT 36263 TED26 connection box | Square 66 x 52mm | EI 90 |
SCHNEIDER Electric IMT 36316 connection box | 3no. plates: 44 x 25mm + 40 x 12mm + 40 x 9mm | E 90, EI 60 |
SCHNEIDER Electric IMT 36356 connection box | Square 45 x 45mm | EI 60 |
- Box not tested separately because the design is the same as ELKO 3012
- Box not tested separately because the design is the same as ELKO 45/6
45x45mm and the 59mm diameter are standard sizes available to order above; other shapes and sizes for specific socket boxes are made to special order - contact our sales team on 0113 2455450 or [email protected] to discuss your requirements.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions . We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Data sheet
- Product Usage Type
- Fire Collar
- Colour Family
- Grey
- Fire Rating
- 30 Minutes
- Fire Rating
- 60 Minutes
- Fire Rating
- 90 Minutes
- Fire Rating
- 120 Minutes
- Fire Rating
- 45 Minutes
Questions
Question about the product
Be the first to ask a question about this product!
IMPORTANT SHIPPING & DELIVERY INFORMATION
Protecta FR Graphite Plate is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT