An ablative-coated stonewool board used to reinstate the fire resistance performance of internal wall and floor constructions where apertures are penetrated by single or multiple services.
- Prevention of air leakage and provides smoke seal
- Maintains Acoustic performance
- Assumed working life 30 years
- Highly flexible, high performance flexible ablative coating, making cutting and install easy
- Lightweight and simple to install
- Tested practically, with the installer in mind
Stopseal 50/60 Fire Batt, an ablative-coated stonewool board used to reinstate the fire resistance performance of wall and floor constructions where apertures arepenetrated by single or multiple services.
The Stopseal Batt is tested and certified as part the FSi Fire Stopping range. The Stopseal Batt can be installed across a variety of services and substrates, including:
- Flexible and Rigid Walls
- Rigid Floors
- Multi-Service penetrations
- Blank Openings
- Head of Walls
Order Reference | Item |
---|---|
FB12500DP48 | Stopseal 50 - 1200 x 600 x 50mm Double Coated Batt |
T1200D | Stopseal 60 - 1200 x 600 x 60mm Double Coated Batt |
T1250SPB | Plain Un-Coated 'Shuttering' 1200 x 600 x 50mm Batt |
Quick Links - Click To Jump To Section:
Features & Benefits
- To reinstate fire resistance through walls and floors
- Multi-service penetrations
- Prevention of air leakage
- Maintains Acoustic performance
- Assumed working life 30 years
- For internal use
- Highly flexible, high performance flexible ablative coating, making cutting and install easy
- Lightweight and simple to install
- Tested practically, with the installer in mind
- Provides smoke seal
- Manufactured and tested alongside the entire FSi Fire Stopping range in the UK
Certification & Testing
- Testing in accordance with EN1366-3:2009 – Fire Resistance
- Classified in accordance with EN13501-2 – Fire Resistance
- CE Marked – ETA 14-0005
- Tested in accordance with ASTM E2923:14 – Longevity of Fire Stop Materials
- Certifire Accreditation – CF513
- ULEU Accreditation
- UAE Certificate of Compliance
- Tested in accordance with EN10140-2:2010 – Airborne Sound
- Tested in accordance with EN1026:2000 – Air Permeability
Technical Data
Description | Result | Test Standards |
---|---|---|
Dimensions | 1200mm x 600mm x 50mm / 1200 x 600 x 60mm | |
Stone Fibre Density | > 140Kg/m³ | |
Coating Thickness | 1mm Nominal, 2.2kg wet film coating | |
Fire Resistance | 4 hours | EN 1366-3; EN 1363-1 EN 13501-2, BS 476 pt 20/22 |
Reaction to fire | Class E | EN 13501-1 |
Insulation (Single Batt) | 142 minutes on seal face, EI 60 | EN 13501-2 |
Insulation (Double Batts) | 264 minutes on seal face, EI 120 | EN 13501-2 |
Acoustic Performance | Acoustic Reduction up to 60dB (Refer to FSi Technical Department for requirements) | EN 10140 |
Air Permeability | 600Pa EN 1026 - 100Pa 1.8/1.4 m3/h/m2 | EN 1026 |
Thermal Conductivity (U Value) | 0.034 W/mK at 10°C | |
Pyrocoustic Sealant coverage | 2.15kg Spread, 2.20kg Spray | |
Maximum Size of Seal | Rigid Wall 5.76m², Floor 2.88m²* | |
Maximum Size - Unsupported Wall | 2880 x 1440mm (4.03m² with services) 1200 x 1200mm (1.44m² with no services) | |
Maximum Size - Unsupported Floor | 1600 x 700mm (1.12m²) | |
Mechanical support* | 30mm x 30mm x 1.6mm steel angle | |
VOC % Nonaqueous volatiles (105°C) | 0.8 | LEED |
Expected Shelf Life | N/A | Must be stored in dry conditions off the floor |
Performance Data
Please refer to the Technical Data Sheet for more information on the following:
- Performance Data - Walls - page 3 - 11
- 100mm Rigid and Flexible Walls
- 150mm Rigid Walls
- Performance Data - Pattress - page 12 - 17
- 75mm Rigid and Flexible Walls
- 100mm Rigid and Flexible Walls
- Performance Data - Floors - page 18 - 19
- 150mm Rigid Floors
- Performance Data - Ducts - page 20 - 22
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Data sheet
- Product Usage Type
- Fire Batt
- Product Range
- Stopseal
- Fire Rating
- 240 Minutes
Questions
Question about the product
Be the first to ask a question about this product!
IMPORTANT SHIPPING & DELIVERY INFORMATION
FSi Stopseal 50/60 Fire Batt is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT