A 2-component polyurethane sealant system, manufactured with halogen-free intumescent fire retardants. On application the two components are mixed through a screw nozzle resulting in a reaction which causes the product to expand and swell around penetrating services. Intended to be used as a mixed penetration seal or cable penetration seal to temporarily or permanently reinstate the fire resistance performance of:
- Flexible wall constructions
- Rigid wall constructions and rigid floor constructions
- Where they have been provided with apertures which are penetrated by various cables, conduits/ tubes, metal pipes, plastic pipes, cable support constructions (perforated or non-perforated steel cable trays and steel ladders.)
- Prevention of air leakage, maintains Acoustic performance
- Assumed working life 10 years
Professional use only - from the 24th August 2023, adequate training is required before industrial or professional use of this product.
Should you require training, visit - https://www.safeusediisocyanates.eu/
Professional use only - from the 24th August 2023, adequate training is required before industrial or professional use of this product. Should you require training, visit - https://www.safeusediisocyanates.eu/
Quick Links - Click To Jump To Section:
Features & Benefits
- Flexible, high performance 2-component PU Sealer
- Expands on application, filling apertures and openings quickly and cleanly
- Conditioned to Type Z1 in accordance with EOTA TR024
- Tested in accordance with many major global certification standards
- Easy gunning and tooling
- Tested practically, with the installer in mind
- Manufactured and tested alongside the entire PyroSeal System range
Certification & Testing
- Tested in accordance with EN1366-3:2009 – Fire Resistance – Penetration Seals
- Classified in accordance with EN13501-2 – Fire Resistance
- Classified in accordance with EN13501-1 – Reaction to Fire
- CE Marked – ETA 18-0897
- Conditioned in accordance with EOTA TR024 – Z1 Type
- Tested in accordance with EN10140-2:2010 – Airborne Sound
- Tested in accordance with EN1026:2016 - Air Permeability
- Tested in accordance with EN12667:2001 & EN12664:2001 - Thermal Properties
Areas of Use
- To reinstate fire resistance through walls and floors
- Prevention of air leakage
- Maintains Acoustic performance
- Assumed working life 10 years
Installation
If the mixing nozzle is clogged, never use force to press out the material, force can destroy the cartridge or the dispensing gun. Wear suitable protective gloves, safety glasses and protective clothing for the work.
- Clean the appature or opening. Cardboard, plastic sheet or duct tape can be used as form work and it can remain on the surface
- Hold the cartridge vertically with the cap pointing upward, unscrew the cap and firmly screw on the provided mixing nozzle
- Insert the cartridge into the intended dispensing gun
- Start pressing out and discard non-mixed initial material
- Fill the opening from back to front. In this process build up the foam from bottom to top, always guide the tip of the mixing nozzle above the foam so that the material does not stick or clog. After a work interruption longer than approximately 50 seconds the foam hardens in the mixing nozzle, which then must be replaced. Prior to changing the mixing nozzle, offload the dispensing gun, and carefully replace the mixing nozzle
- After approx. 2 minutes projecting foam residues can be cut off with a suitable knife in compliance with the necessary protective measures and safety regulations
- Cables or pipes that will be installed retroactively can be routed through the existing foam. Refill gaps due to removed cables or pipes with PyroSeal 2k
- Large free areas can be filled with PyroSealBricks
Processing of PyroSeal Brick
- Areas that are not penetrated by cables, cable support systems, conduits or pipes can be sealed with PyroSeal Brick
- The PyroSeal Brick must be installed in such a manner that the minimum seal thickness is maintained
- Remove the protective foil of the PyroSeal Brick and install them in layers (like in a brick wall, i.e. layer-by-layer offset of the vertical butt joints) so that they fit tightly in the opening
Performance Data
Refer to data sheet for performance data for floors, walls, Direct field of application – DiAP and Extended Field of Application- EXAP
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Data sheet
- Manufacturer
- FSi
- For Use By
- Professional Use
- Interior / Exterior Use
- Interior Use
- For Use On
- Walls
- For Use On
- Floors
- Pack Size
- 380ml Cartridge
- Suitable For Use On
- Walls
- Suitable For Use On
- Floors
- Application Method
- Application Gun
- Usages
- Fire Protection Sealants
- Product Usage Type
- Sealer
- Colour Family
- Red
- Colour Family
- Brown
Questions
Question about the product
Be the first to ask a question about this product!
IMPORTANT SHIPPING & DELIVERY INFORMATION
FSi PyroSeal 2K Fire Resistant Expanding Sealer is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT