One component solvent based acrylic thin film intumescent coating independently approved for fire protection of structural steel exposed to cellulosic fire. It can be used as a mid coat or finish coat in atmospheric environments and is suitable on approved primers on carbon steel and galvanised steel substrates.
- Specially designed as a reactive fire protection system for steel constructions
- Suitable for structural steel for internal or semi-exposed locations up to corrosivity category C4 (ISO 12944-2), with an approved topcoat
Please Note: SteelMaster 60SB can be exposed without topcoat for 3 months during construction phase or up to 6 months with an approved topcoat. Whether topcoated or not, the coating must be protected from condensation, ponding/ pooling water due to rainfall or running water, provided it has had appropriate drying prior to exposure. This also extends to snow and ice.
Please Note: We strongly recommend Tricomb Plastic Wet Film Gauges are used to help ensure correct film thicknesses are achieved during application
Jotun Steelmaster 60SB is a one component solvent based acrylic thin film intumescent coating independently approved for fire protection of structural steel exposed to cellulosic fire. It can be used as a mid coat or finish coat in atmospheric environments and is suitable on approved primers on carbon steel and galvanised steel substrates.
Typical Uses
Specially designed as a reactive fire protection system for steel constructions. Suitable for structural steel for internal or semi-exposed locations up to corrosivity category C4 (ISO 12944-2), with an approved topcoat.
Please Note: SteelMaster 60SB can be exposed without topcoat for 3 months during construction phase or up to 6 months with an approved topcoat. Whether topcoated or not, the coating must be protected from condensation, ponding/ pooling water due to rainfall or running water, provided it has had appropriate drying prior to exposure. This also extends to snow and ice.
Quick Links - Click To Jump To Section:
Features & Benefits
- Majority of steel sections covered
- Easy airless spray application
- Ready to use
- Reduced application time
- Reduced site costs
Certifications
- BS 476 part 20/21: Certifire CF 5170
- EN 13381-8
- CE marked product with European Technical Assessment ETA-20/1294
- Durability and Serviceability: Z2, Z1, Y (ETAG 018-2)
- ASTM E84: Class A
Additional certificates and approvals may be available on request.
Application Notes
The product can be applied by:
Spray - Use airless spray
Brush - Recommended for stripe coating and small areas, care must be taken to achieve the specified dry film thickness.
For the full guidance notes download the Steelmaster product Application Guide from the 'Data Sheets' Tab above.
Drying Times
Substrate Temperature | 5°C | 10°C | 23°C | 40°C |
---|---|---|---|---|
Surface (touch) dry | 2 h | 1 h | 30 min | 20 min |
Dry to handle | 48 h | 24 h | 16 h | 8 h |
Dry to over coat, minimum | 24 h | 8 h | 6 h | 6 h |
For maximum overcoating intervals, refer to the Application Guide (AG) for this product.
Dry to overcoat minimum is with self. See additional guidance for Topcoating.
- All drying times have been measured at a wet film thickness of 1000 μm under controlled temperature and relative humidity below 85 %
- Drying times can vary depending on environmental conditions such as air temperature, relative humidity, weather conditions, ventilation and also the number of coats, total dry film thickness applied, etc.
Topcoating
- The recommended minimum overcoating interval of this product with approved acrylic topcoats is 24 hours and for other approved topcoats is 48 hours
- The system should be dry to handle and coating thickness gauge should not leave an indentation on the coating
- Drying time/overcoating interval may be extended if there is a drop in temperature or if multi-coat system is applied
- Prior to application of topcoat, the applicator must ensure that the specified dry film thickness has been achieved
- Surface (touch) dry: The state of drying when slight pressure with a finger does not leave an imprint or reveal tackiness
- Dry to handle: Minimum time before the coated objects can be handled without physical damage
- Dry to over coat, minimum: The recommended shortest time before the next coat can be applied
Important Notes
Pre-commissioning considerations
Off-site application:
- During the following given operations, damage to the coating system can occur particularly between in-shop applications through to final erection on site
- For transportation of the applied sections from the fabrication yard to the erection site, the complete system with approved topcoat must be applied
- Systems must be allowed to hard dry and approved before movement to site
Handling
- Coatings should be sufficiently dry before handling and members should be lifted at designated lifting points or by using lifting brackets where available
- The use of appropriate lifting chains or slings to be considered to minimise damage to coated steel
- Single lift should be used unless specially designed multi-lift cradles are available
- It should be noted that the potential for damage increases with coating thickness, as does the difficulty of repair
Transportation
- The loading of trailers should be carefully planned, with timber supports positioned, where possible, in uncoated contact areas (e.g. areas to receive bolted connections)
- Where contact of supports with coated areas is unavoidable, members should be supported on their toes to minimise the contact area
- Members which may fill with water should be prevented from doing so by the use of covers which will not react with the intumescent coating system, should they come into contact
- Loads are best secured with the careful use of clean chains, and it is advised that loaders wear overshoes and where possible avoid walking on coated surfaces in order to minimise contamination
Storage
- Where site storage is unavoidable, similar care should be taken in the handling and support of the coated steel using the same lifting and support points as those used in transportation
- The steelwork must be stored off ground and under cover both at the application facility and once transported to site
- Any temporary covers must allow ventilation to prevent a humid atmosphere building up around the steelwork
- Once dried occasional condensation is acceptable, but this must not amount to ponding or running water
- Protect from frost and snow
- Storage areas should be roped off with signage clearly explaining the need to avoid contamination and mechanical damage to the coated steelwork
Please see the Product Data Sheet and Application Guide for detailed guidance.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Data sheet
- Manufacturer
- Jotun
- For Use By
- Professional Use
- Interior / Exterior Use
- Interior & Exterior
- Single, Two or Three Pack
- Single
- Application
- Brush, Spray
- Touch Dry
- 30 mins
- Dry to Recoat (at 23°C)
- 6 hours
- Base Type
- Solvent-Based
- Suitable For Use On
- Steel
- Application Method
- Brush
- Application Method
- Spray
- Product Usage Type
- Basecoat
- Product Range
- Steelmaster
- Colour Family
- White
- Fire Rating
- 30 Minutes
- Fire Rating
- 60 Minutes
- Site Application
- On-Site
- Site Application
- Off-Site
Questions
Question about the product
bayo sawa on 2020-11-19 09:18:05 | Question:
what is the coverage of this paint per m2 |
Answer from Rawlins’ Technical Team:
There is no coverage rate per m² for this product. The Intumescent must be applied at the specified WFT. If you require assistance with a specification please contact our Technical Team on 0113 2545450 option 2. | |
IMPORTANT SHIPPING & DELIVERY INFORMATION
Jotun Steelmaster 60SB is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT
Tricomb Plastic Wet Film Gauges (W2008)
Ensures the quality control of the paint thickness while the coating is still wet. Applying too much coating can be expensive. Wet film measurements are also useful for coatings where the dry film thickness can only be measured destructively. More Information Delivery Info
Surface Preparation Kits for Steel
These surface preparation kits for steel have been created to help provide customers with an easily accessible bundle of tools to aid in the preparation of steel surfaces in accordance with ISO 8501-1 (St2/3) and SSPC (SP 2/3). Please click here for important information about these kits. Kit Contents: SET 1 (Hand Tools) 1 x Rust-Oleum...