Nullifire FV125 Large Ventilated Cavity Barrier

FV125
NUL10785

Suited to an open state cavity with a maximum air gap of 25mm and consists of a specially formulated fire rated rock mineral fibre section with an integral high expansion intumescent seal attached to the leading edge.

It is essential that the correct fire barriers are specified and installed, therefore in order to make a purchase you must fill in the application form by clicking on the button below. Our technical team will then contact you with the required specification and a link to place an order*.

Application Form

*Please Note Providing limited or insufficient information will only trigger a response from the Technical Team requesting further details before they can make a recommendation and provide a link to purchase the products.

  • Up to 180 minutes fire resistance* tested in accordance with ASFP TGD19 guidance
  • Maintains a 25mm air gap
  • Up to 450mm cavities tested
  • Fixing brackets included as standard
  • Length 1000mm - Height 75mm - Thickness 4mm
  • Available in a wide range of sizes from 35mm to 425mm wide

Please note: This product is made to order subject to an extended lead time of 10 working days

*Optimised for 60 mins - see Performance Table in 'Data Sheets' tab

Item
£25.12(incl. VAT)
£20.93(ex. VAT)
Quantity
Please choose your colour
This Product is Price on Application Only

Description

Nullifire FV125 Large Ventilated Cavity Barrier is a fire rated product designed to act as an external wall cavity barrier at the required locations such as compartment floors, around windows, doors, etc. and within uninsulated cavities requiring permanent (open-state) ventilation, to reinstate fire resistance performance.

In the event of a fire FV125 will expand to close the final gap between its leading edge and the internal face of the cladding. It provides effective fire resistance, for integrity and insulation for up to 180 minutes depending upon the construction of the external walls.

FV125 is designed for use within a designed cavity of up to 450mm cavity, and once installed will close the remaining free air gap (in front of the 4mm thick cavity barrier) of 25mm.



Quick Links - Click To Jump To Section:




Features & Benefits


       
  • Up to 180 minutes fire resistance tested in accordance with ASFP TGD19 guidance
  • Designed for use within a designed cavity of up to 450mm cavity, and once installed will close the remaining free air gap (in front of the 4mm thick cavity barrier) of 25mm
  • Maintains a 25mm air gap
  • Up to 450mm cavities tested
  • Fixing brackets included as standard
  • Allows ventilation of cavities reducing the need for cavity trays or weepholes
  • Lightweight for easy and quick installations
  • No maintenance required after installation
  • Available in a wide range of sizes from 35mm to 425mm wide



Available Sizes and Order References


Product Code Description Size
FV125605935 Large Ventilated Cavity Barrier 25 mm Air Gap 60 mm 35 x 75 x 1000 mm
FV125605936 Large Ventilated Cavity Barrier 25 mm Air Gap 70 mm 45 x 75 x 1000 mm
FV125605937 Large Ventilated Cavity Barrier 25 mm Air Gap 80 mm 55 x 75 x 1000 mm
FV125605938 Large Ventilated Cavity Barrier 25 mm Air Gap 90 mm 65 x 75 x 1000 mm
FV125605939 Large Ventilated Cavity Barrier 25 mm Air Gap 100 mm 75 x 75 x 1000 mm
FV125605940 Large Ventilated Cavity Barrier 25 mm Air Gap 110 mm 85 x 75 x 1000 mm
FV125605941 Large Ventilated Cavity Barrier 25 mm Air Gap 120 mm 95 x 75 x 1000 mm
FV125605942 Large Ventilated Cavity Barrier 25 mm Air Gap 130 mm 105 x 75 x 1000 mm
FV125605943 Large Ventilated Cavity Barrier 25 mm Air Gap 140 mm 115 x 75 x 1000 mm
FV125605944 Large Ventilated Cavity Barrier 25 mm Air Gap 150 mm 125 x 75 x 1000 mm
FV125605945 Large Ventilated Cavity Barrier 25 mm Air Gap 160 mm 135 x 75 x 1000 mm
FV125605946 Large Ventilated Cavity Barrier 25 mm Air Gap 170 mm 145 x 75 x 1000 mm
FV125605947 Large Ventilated Cavity Barrier 25 mm Air Gap 180 mm 155 x 75 x 1000 mm
FV125605948 Large Ventilated Cavity Barrier 25 mm Air Gap 190 mm 165 x 75 x 1000 mm
FV125605949 Large Ventilated Cavity Barrier 25 mm Air Gap 200 mm 175 x 75 x 1000 mm
FV125605950 Large Ventilated Cavity Barrier 25 mm Air Gap 210 mm 185 x 75 x 1000 mm
FV125605951 Large Ventilated Cavity Barrier 25 mm Air Gap 220 mm 195 x 75 x 1000 mm
FV125605952 Large Ventilated Cavity Barrier 25 mm Air Gap 230 mm 205 x 75 x 1000 mm
FV125605953 Large Ventilated Cavity Barrier 25 mm Air Gap 240 mm 215 x 75 x 1000 mm
FV125605954 Large Ventilated Cavity Barrier 25 mm Air Gap 250 mm 225 x 75 x 1000 mm
FV125605955 Large Ventilated Cavity Barrier 25 mm Air Gap 260 mm 235 x 75 x 1000 mm
FV125605956 Large Ventilated Cavity Barrier 25 mm Air Gap 270 mm 245 x 75 x 1000 mm
FV125605957 Large Ventilated Cavity Barrier 25 mm Air Gap 280 mm 255 x 75 x 1000 mm
FV125605958 Large Ventilated Cavity Barrier 25 mm Air Gap 290 mm 265 x 75 x 1000 mm
FV125605959 Large Ventilated Cavity Barrier 25 mm Air Gap 300 mm 275 x 75 x 1000 mm
FV125605960 Large Ventilated Cavity Barrier 25 mm Air Gap 310 mm 285 x 75 x 1000 mm
FV125605961 Large Ventilated Cavity Barrier 25 mm Air Gap 320 mm 295 x 75 x 1000 mm
FV125605962 Large Ventilated Cavity Barrier 25 mm Air Gap 330 mm 305 x 75 x 1000 mm
FV125605963 Large Ventilated Cavity Barrier 25 mm Air Gap 340 mm 315 x 75 x 1000 mm
FV125605964 Large Ventilated Cavity Barrier 25 mm Air Gap 350 mm 325 x 75 x 1000 mm
FV125605965 Large Ventilated Cavity Barrier 25 mm Air Gap 360 mm 335 x 75 x 1000 mm
FV125605966 Large Ventilated Cavity Barrier 25 mm Air Gap 370 mm 345 x 75 x 1000 mm
FV125605967 Large Ventilated Cavity Barrier 25 mm Air Gap 380 mm 355 x 75 x 1000 mm
FV125605968 Large Ventilated Cavity Barrier 25 mm Air Gap 390 mm 365 x 75 x 1000 mm
FV125605969 Large Ventilated Cavity Barrier 25 mm Air Gap 400 mm 375 x 75 x 1000 mm
FV125605970 Large Ventilated Cavity Barrier 25 mm Air Gap 410 mm 385 x 75 x 1000 mm
FV125605971 Large Ventilated Cavity Barrier 25 mm Air Gap 420 mm 395 x 75 x 1000 mm
FV125605972 Large Ventilated Cavity Barrier 25 mm Air Gap 430 mm 405 x 75 x 1000 mm
FV125605973 Large Ventilated Cavity Barrier 25 mm Air Gap 440 mm 415 x 75 x 1000 mm
FV125606131 Large Ventilated Cavity Barrier 25 mm Air Gap 450 mm 425 x 75 x 1000 mm



Necessary Tools & Preparation


Necessary Tools

  • Masonry drill
  • Screwdriver
  • Saw/knife for cutting product
  • Measuring tape
  • Stainless steel fixings suited to the substrate

Preparation

  • Ensure the installation area is free from dust, oil and any corrosive material
  • Check the mounting substrate is solid and free from damage and degradation before beginning
  • Double check for any obstructions, ensure that if there are any that could allow fire to pass vertically, they are fire stopped separately using an approved and applicable Fire Stopping product



Application Instructions


FV125 from 40 mm up to 100 mm wide - NO brackets required and directly faced fixed

  • Use stainless steel countersunk head screws, with a maximum head diameter of 11.5mm and with a length suitable for the size of cavity barrier and sufficient fixing depth into the substrate
  • Fixings must have an appropriate fixing depth (embedment) into the substrate (with a minimum of 50mm for masonry fixings and minimum 25 mm for timber unless otherwise specified by the fixing manufacturers guidance for their fixing type)
  • Ensure that the countersunk screw head does not fully penetrate the face of the cavity barrier, the screw head should sit flush or slightly proud. See figure below
  • Care should be taken not to over tighten as this may affect the performance of the intumescent seal
  • Position the first screw fixing through the centre line of the face of the cavity barrier at a maximum 125mm from one end, continue to face fix through at maximum 250mm centres (4 screws per linear metre), ensuring that the final fixing is a maximum 125 mm from the opposite end of the cavity barrier. This will ensure that face fixings are positioned at 250mm maximum centres across the continuous run of cavity barrier

NOTES:

  • Where sections of cavity barrier are less than 1 linear metre in length, ensure that face fixings are positioned at a maximum 125mm from each end with additional fixing being positioned at maximum 250mm centres between the end fixings
  • For cut sections of cavity barrier less than or equal to 250 mm in length a minimum of 2 fixings are required



Bracket Fixing

  • FV125 is supplied with 2 or 3 fixing spikes, FO306 Small Steel brackets, dependent on requirement
  • The central section is pre-drilled to secure the bracket to the substrate
  • Option A, from the image below, will protrude 65mm or Option B will protrude 160mm from the face of the substrate
  • If the bracket protrusion is greater than 75% of the product width, the bracket shall be cut down in length
  • The bracket should never be less than 50% of the product width

NOTES:

  • FV125 above 100mm are required to be mounted on Stainless Steel brackets (FO306 Small Steel Brackets 65mm)
  • The number of brackets required is dependent upon the width of the overall cavity



Application Instructions with Brackets

  • To secure the bracket use nom. 5mm stainless steel screws/fixings, with a maximum head diameter of 13mm and with a length and type suitable for the substrate. See Performance Data Table
    • Notes:
    • Ensure that the screw head sits as flush as possible with the substrate
    • Fix through both of the fixing holes
    • Fixings must have an appropriate fixing depth for the substrate (with a minimum of 50mm for masonry and minimum 25mm for timber unless otherwise specified by the fixing manufacturers guidance for their fixing type)

  • Fix the required number of brackets, per linear metre, to the substrate at maximum 250mm from the end of the cavity barrier, with a maximum spacing between brackets of 500mm
    • Notes:
    • Excluding cavity width 241mm to 425mm which requires 3 brackets
    • Where sections of cavity barrier are less than 1 linear metre in length, ensure that the brackets are positioned at a maximum 250mm from each end. For cut sections of cavity barrier less than or equal to 500mm in length two brackets are required

  • Push the cavity barrier onto the bracket spike, the brackets should impale FV125 to mid barrier depth and must not protrude through the intumescent element
  • Ensure the cavity barrier should be pushed fully onto the bracket spike and sit flush with the substrate at the rear of the cavity barrier, ensuring that there are  no gaps behind the cavity barrier                                             
  • Ensure that the spike does not pierce through the face of the intumescing material



Important Information


  • Maximum free air gap for this cavity barrier is 25mm, the space in front of the intumescing strip on the face of the cavity barrier to the rear of the external wall surface
  • Ventilated cavity barriers should be installed in a continuous run (with the exception of abutting up to full fill vertical cavity barriers). Where this is not possible, details should be agreed with the project's principal designer and a fire engineer
  • Horizontal cavity barriers should be installed adjacent and tightly abutted to any vertical cavity barriers, the vertical cavity barriers should be installed first
  • An identification label is attached to the intumescing face of the cavity barrier, ensure this faces out into the open cavity. Also ensure the label is visible and legible and reads the right way up. If the identification label is not legible please contact Technical Support, the label is important in terms of identifying the product in the future, for example during fire risk assessments or fire safety inspections
  • Cavity barrier fixing brackets, both Small (FO306 Stainless Steel Brackets) or Large Steel Brackets (FO307 Large Steel Brackets) must not penetrate through the face of the cavity barrier. Screws for direct fixing and fixings to secure brackets are not supplied by Nullifire
  • The brackets used to fix the horizontal cavity barrier must be installed with the spike inserted centrally (horizontally) to the rock mineral wool section of the cavity barrier with the bracket fixed above and not below the cavity barrier
  • The use of tape is not required over the joints between the lengths of cavity barrier, and if used should not be applied over the face of intumescent material
  • The cavity barrier must be installed following the installation methods described above. The cavity barrier must not be penetrated by any other mechanical or electrical services



Technical Information


Property Value
Fire Resistance: TGD19 Up to 180 minutes (see Performance Table in 'Data Sheets' tab)
Composition Flexible intumescent material roll
Free Expansion 26:1 Ratio
Durability Type X intended for use in conditions exposed to weather (UV, rain, frost)
Maximum Continuous Operating Temperature 80°C
Smoke / Halogen Content Low smoke / Zero halogen
Service Temperature -20°C to +70°C
Storage Store in dry, ambient conditions between -20°C and +70°C
Shelf Life 60 years



Maintenance


  • No active maintenance required
  • Where alterations are made around the product it should be checked visually to ensure that the product is still installed as per the approved original design and fitting instructions at the time of original installation



IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.



Product Details
10785-994269

Data sheet

Manufacturer
Nullifire
For Use By
Professional Use
Suitable For Use On
External Wall Cavities
Application Method
Hand
Manufacturer
Nullifire
Usages
Fire Stopping
Product Usage Type
Fire Barrier
Product Usage Type
Ventilated Cavity Barrier
Fire Rating
Up to 180 minutes fire resistance tested in accordance with ASFP TGD19 guidance
Fire Rating
180 Minutes
Cavity Width
35mm - 425mm
Attachments
Download


Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.


Be the first to ask a question about this product!


Question about the product

* Required fields
(read)
Send

IMPORTANT SHIPPING & DELIVERY INFORMATION

Nullifire FV125 Large Ventilated Cavity Barrier is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.

Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.

Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.

All delivery costs below are excluding VAT


You might also like