Protecta FR Damper

PRO-DAMPER
PRO4261

Fire proofs ventilation ducts that pass through fire-rated walls & floors, preventing spread of fire & smoke both surrounding & inside  ducts. The steel casing contains horizontal steel blades treated with a technically advanced heat expanding graphite, closing off the damper in fire.

  • Closes in the area where the fire is located but not elsewhere - allows ventilation systems to extract smoke from areas that are not on fire
  • Maintenance free - no electrical connections necessary - same damper can be installed in both walls & floors, & can be attached to a vent on one side
  • Keeps the temperature in the duct network lower than 120°C & will therefore protect fans & sensitive units in the system
  • Service life of more than 50 years; the damper will last the same life cycle as the ventilation system
  • Fits standard ducting equipment
  • Space saving - dampers are attached to the inside of ducts - no insulation required
  • See below for technical & test data

Please note P208 - 1250mm Diameter is available as POA subject to an extended lead time.

Colour
Item
£40.25(incl. VAT)
£33.54(ex. VAT)
Quantity
Please choose your colour
Available for Delivery (See Delivery Options Below)

questions 1 question about the product
Description

Protecta FR Damper, part of the Protecta Firestopping range, fire proofs ventilation ducts where they penetrate fire rated constructions such as fire compartments in floors and fire walls, preventing the passage of fire and smoke both surrounding and inside the ventilation duct.

It consists of a steel casing containing horizontal steel blades treated with a technically advanced heat expanding graphite which closes off the whole damper in a fire. The aperture surrounding the dampers are fire sealed with Protecta FR Board in walls and Protecta EX Mortar in floors.

The damper can be installed in the fire seal and the ventilation ducting attached or the damper can be connected to the ducting and then fire sealed.

The aperture where the ducts pass through can include one or multiple ventilation ducts. One can also pass through other technical services such as cables, cable trays and pipes within the same aperture.



Features & Benefits


  • Fire protection for air ventilation ducts in walls and floors.
  • Intumescent graphite material expands in fire to seal gaps.
  • Prevents spread and penetration of smoke and fire both surrounding and inside the ventilation duct.
  • Closes in the area where the fire is located but not elsewhere so the ventilation system can be used to extract smoke from areas that are not on fire.
  • Maintenance free and no electrical connections necessary.
  • The same damper can be installed in both walls and floors.
  • Keeps the temperature in the duct network lower than 120°C and will therefore protect fans and sensitive units in the system.
  • Insulation of ducts is not necessary.
  • Service life of more than 50 years; the damper will last the same life cycle as the ventilation system.
  • Designed to fit standard ducting equipment so that the ducting system installer can easily fit the dampers.
  • Space saving - the dampers are attached to the inside of the ducts
  • An aperture can include several dampers and in addition technical services such as cables, cable trays and pipes.
  • Dampers are only 15 cm long and bends can be connected right behind the fire seal (can also be special ordered in other sizes).
  • The damper can be attached to a vent on one side.



Ordering References


Reference Product Name Size Colour Weight
P195 Protecta FR Damper 63mm Diameter Grey 0.51 kg
P196 Protecta FR Damper 80mm Diameter Grey 0.68 kg
P197 Protecta FR Damper 100mm Diameter Grey 1.24 kg
P198 Protecta FR Damper 125mm Diameter Grey 1.57 kg
P199 Protecta FR Damper 160mm Diameter Grey 2.35 kg
P200 Protecta FR Damper 200mm Diameter Grey 3.36 kg
P201 Protecta FR Damper 250mm Diameter Grey 3.90 kg
P202 Protecta FR Damper 315mm Diameter Grey 7.36 kg
P203 Protecta FR Damper 400mm Diameter Grey 11.28 kg
P204 Protecta FR Damper 500mm Diameter Grey 14.60 kg
P205 Protecta FR Damper 630mm Diameter Grey 20.90 kg
P206 Protecta FR Damper 800mm Diameter Grey 32.24 kg
P207 Protecta FR Damper 1000mm Diameter Grey 49.80 kg
P208 Protecta FR Damper 1250mm Diameter POA Grey 74.00 kg

The length of the dampers in the table are 150mm plus overlap/ connection for the ventilation ducts. Longer and shorter dampers can be manufactured on request.

Protecta FR Damper for rectangular ducts are manufactured to precise measurements, and are not standard goods.

Contact our sales team on 0113 2455450 or [email protected] to discuss your fire-stopping projects and requirements.



Technical Data


Appearance Ready manufactured in steel and graphite
BREEAM Approved, EC1 PLUS on all fire seals
Interior climate, installed Z 2 : Relative air moisture up to 85% and temperatures between 5 and 40°C
Trigger-temperature in fire 100°C
Temperature, full closure 160°C
Time to full closure From 50 seconds to 2 minutes
Expansion rate graphite 15.5 to 17
Density graphite 2.6 kg per ltr
Thickness graphite 1.6 mm
Leakage classification Class C according to EN 1751 (circular)
Free air opening Between 84.2% and 85.4%
Pressure in fire FR Damper resists minimum 300Pa
Standard for connections EN 1506:2007
Standard for fire testing EN 1366-12:2014 & EN 1363-1:2012
Standard for aerodynamics EN 1751:2014
Standard for sound levels EN ISO 5135:1998
Storage In temperatures between 5°C and 30°C
Life span Under normal conditions; 50 years +
Installation temperature +5°C to +50°C
Colour Galvanized steel with section of red colour to identify placement of the fire seal



Fire Resistance


Construction Description Classification
Flexible and rigid walls with thickness ≥ 100mm ≤ Ø 400mm FR Damper/duct with ≥ 200mm stone wool mat on both sides EI 120 (E 120)
≤ Ø 1250mm FR Damper/duct with ≥ 500mm stone wool mat on both sides EI 60 (E 90)
≤ 600mm high x 1000mm wide FR Damper/duct with ≥ 500mm stone wool mat on both sides EI 120 (E 120)
≤ 1200mm high x 1700mm wide FR Damper/duct with ≥ 500mm stone wool mat on both sides EI 90 (E 90)
Rigid floors with thickness ≥ 150mm ≤ Ø 400mm FR Damper/duct with ≥ 150mm stone wool mat on top side EI 120 (E 180)
≤ Ø 1000mm FR Damper/duct with ≥ 500mm stone wool mat on top side EI 90 (E 90)
≤ 600 x 1000mm FR Damper/ duct with ≥ 500mm stone wool mat on top side EI 60 (E 90)
≤ 1000 x 1000mm FR Damper/ duct with ≥ 500mm stone wool mat on top side EI 90 (E 90)

The stone wool mat described is with thickness ≥ 30mm and density ≥ 80kg/m³ with or without aluminium foil, attached according to the products installation instructions.



The ‘close in and pull out’ Principle


A combined close in and pull out solution prevents spread of fire by closing off the fire inside the fire compartment, using the ventilation system outside the area of the fire to pull out any smoke that filters out through the fire compartments constructions.

Protecta FR Dampers have to be used in all ventilation duct penetrations in fire compartments and fire walls, closing off the fire compartment but not in the parts of the building that are not on fire. For the principle to work effectively it is recommended that the ventilation unit is protected with a battery backup and a by-pass of the filters so that the smoke from the fire does not blind them.

When using Protecta FR Dampers the ventilation ducts do not need to be fully insulated.



Dust Formation and General Maintenance


Tests conducted on Protecta FR Damper to determine dust formation inside the damper show that dust does not collect inside the damper, and no more than in any other components in the ventilation system. The dust has a tendency to be blown through the dampers as long as the ventilation system is in constant operation and installed in normal indoor environments (Z 2).

It is recommended that the ventilation system is designed and cleaned according to local regulations and building codes to provide access for inspections and cleaning, along with the frequency of these cleaning routines. Protecta FR Damper can easily be cleaned using a vacuum cleaner if this should be needed. Ducts from kitchens and similar, where there is the risk of grease and high humidity, must be fitted with grease filters or similar that are cleaned at fixed frequencies.



Minimum Distances and Limitations


The maximum size of an aperture is 1200 x 2400mm in floors and 1500mm height x 2400mm width or 1200mm height x unlimited width in walls. An aperture can include several services, and they may also include a combination, e.g. cables, cable trays and pipes.

The minimum permitted separation between adjacent seals/ apertures is 200mm. Services should be a minimum of 25mm from seal edges. Services within the system Protecta fire seal do not require a minimum separation, except when pipes where combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. There must be sufficient distance between two ventilation ducts so that the fire seal can be constructed as stated in the installation instructions.



Supporting Constructions


Flexible walls must have a minimum thickness of 100mm and comprise steel studs or timber studs*** lined on both faces with minimum 2 layers of 12.5mm thick boards.

Rigid walls must have a minimum thickness of 100mm and comprise concrete, aerated concrete or masonry, with a minimum density of 650 kg/m³.

Rigid floors must have a minimum thickness of 150mm and comprise aerated concrete or concrete with a minimum density of 650 kg/m³.

The supporting construction must be classified in accordance with EN 13501-2 for the required fire resistance period.

***Timber studs: no part of the penetration seal may be closer than 100mm to a stud, and minimum 100mm of insulation of class A1 or A2 according to EN 13501-1 must be provided within the cavity between the penetration seal and the stud.



Sound Insulation


Description Sound Classification
Protecta FR Board in wall 55 dB
Protecta EX Mortar in floor 64 dB

The sound insulation values are valid for the fire seal only and not any other components in the construction, as for instance the ventilation ducts.

Protecta products has been tested at BM Trada (UKAS accredited); according to EN ISO 10140-2:2010.



Casing Leakage Classification


Protecta FR Dampers are fitted with high quality gaskets in circular ducts, and are tested according to EN 1751 to the highest possible class C for all sizes. Testing was conducted at BRE’s accredited laboratory and test reports can be provided upon request.

Case leakage classification for rectangular dampers is dependent on which locking mechanism is chosen, and the classification will be the same as the classification of the locking mechanism used. Polyseam can deliver dampers with most common types of locking mechanisms that are available in the marketplace.



Loadbearing Properties in Floors


Protecta EX Mortar has been subject to concentrated load and impact tests in floors according to ETAG 026-2 and EOTA TR001 Clause 2. The tests were conducted on the minimum allowed cast depth of 100mm.

According to the loading limits in the table below, reinforcement is not necessary, however it is highly recommended that the edges of the aperture are brushed free of any dust or loose particles and that any contamination is washed away using clean water. Moistening the edges well before casting will improve adhesion.

Protecta EX Mortar should not be cast in surface treated concrete. The mortar must be mixed to a thick but fluid mass at a rate of approx. 2 parts of powder to 1 part water. Maximum loadbearing performance will be achieved 28 days after casting.

Test results:

Test in 1500x1000mm frame Results
Soft body impact, serviceability 500Nm
Soft body impact, safety in use 700Nm
Hard body impact, serviceability 6 Nm
Hard body impact, safety in use 10 Nm
Concentrated load to ETAG 26-2 15 kN



Application Instructions


Installation Instructions in Flexible Walls

  1. Before installing Protecta FR Board ensure that the surface of all service penetrations and surrounding construction is free from all loose contaminants, dust and grease.
  2. Protecta FR Coating and Protecta FR Acrylic are water based, so in cases where corrosion protection is a problem, some metals may require a barrier between the seal and the surface prior to this installation.
  3. Use the product Protecta FR Board 1-S 50mm with two boards in the aperture. The coated side of the board should be flush with the surface of the wall on both sides.
  4. When fire sealing shaft walls consisting of gypsum only on one side, subject to authority approval, install Protecta FR Board on the exposed side only.
  5. Cut the required board(s) to suit the aperture dimensions and type and size of service penetration(s). All exposed and cut edges of the board can be sealed with Protecta FR Coating or Protecta FR Acrylic prior to fitting which will act as an adhesive and ensure a smoke tight seal.
  6. Cut a hole for the damper and glue the damper into the boards with Protecta FR Acrylic or Protecta FR Coating.
  7. All joints, gaps or imperfections in the installed seal must be filled with Protecta FR Acrylic on both sides.
  8. Connect the ventilation ducts to the damper.
  9. Insulate the duct towards the fire seal on both sides with 30mm thick stone wool mat in lengths given in the Fire Resistance Table above. If the duct is ending in the wall then insulate on one side only.
  10. Protecta FR Board can be over-painted with most emulsion or alkyd (gloss) paints.

 

Installation Instructions in Rigid Walls

  1. Before installing Protecta FR Board ensure that the surface of all service penetrations and surrounding construction is free from all loose contaminants, dust and grease.
  2. Protecta FR Coating and Protecta FR Acrylic are water based, so in cases where corrosion protection is a problem, some metals may require a barrier between the seal and the surface prior to this installation.
  3. Use the product Protecta FR Board 1-S 50mm with two boards in the aperture. The coated side of the board should be flush with the surface of the wall on both sides, but not at such distance so the ends of the damper is covered.
  4. Cut the required board(s) to suit the aperture dimensions and type and size of service penetration(s). All exposed and cut edges of the board can be sealed with Protecta FR Coating or Protecta ® FR Acrylic prior to fitting which will act as an adhesive and ensure a smoke tight seal.
  5. Cut a hole for the damper and glue the damper into the boards with Protecta FR Acrylic or Protecta FR Coating.
  6. All joints, gaps or imperfections in the installed seal must be filled with Protecta FR Acrylic on both sides.
  7. Connect the ventilation ducts to the damper.
  8. Insulate the duct towards the fire seal on both sides with 30mm thick stone wool mat in lengths given in the Fire Resistance Table above. If the duct is ending in the wall then insulate on one side only.
  9. Protecta FR Board can be over-painted with most emulsion or alkyd (gloss) paints.

 

Installation Instructions in Rigid Floors

  1. Ensure the faces of the aperture opening are free of dust and any other contaminants. The faces may be moistened for better adhesion.
  2. Bare metal pipes or similar passing through the seal must be protected against corrosion using a suitable primer/protection system.
  3. Install the damper in the aperture with a temporary support, for instance with the shutter board.
  4. Install a stone wool shutter board or another type of shutter to achieve the required 100mm thickness of mortar. Make sure that this achieves a very tight seal – any small openings should be sealed with Protecta FR Acrylic.
  5. Pour clean water into a suitable mixing vessel and pour enough mortar to obtain the required consistency. Mix well to avoid lumps. Always add the mortar to the water, do not reverse this mixing process. For different mix ratios and drying times, please refer to the mortar’s Technical Data Sheet.
  6. Once the desired consistency is achieved pour or trowel the mortar onto the shutter board making sure that it flows into all corners and around services. Apply a firm pressure to the mortar to eliminate any trapped air bubbles. Build up to the required depth of 100mm.
  7. Connect the ventilation ducts to the damper.
  8. Insulate the duct towards the fire seal on the top side with 30mm thick stone wool mat in lengths given in the Fire Resistance Table above



Pressure Differences & Sound Power Levels


Refer to the Product Data Sheet for data tables and line graphs.

 

IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions . We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.

Product Details
4261-555539

Data sheet

Product Usage Type
Fire Collar
Colour Family
Grey
Fire Rating
60 Minutes
Fire Rating
90 Minutes
Fire Rating
120 Minutes
Attachments
Download


Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.

Questions

Question about the product

* Required fields
(read)
questions Nigel Ellis on 2024-07-26 10:26:42
Question: 

Is this suitable for bathroom extractor fan which expels into a garage?

Answer from Rawlins’ Technical Team:

No, this product isn't suitable for installation with an extractor fan.

Please e-mail [email protected] with further application details to allow us to assist with an alternative product.

IMPORTANT SHIPPING & DELIVERY INFORMATION

Protecta FR Damper is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.

Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.

Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.

All delivery costs below are excluding VAT