- There are no more items in your cart
- Shipping Calculated at checkout
-
Sub-Total (inc. VAT)
£0.00
Specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. They will seal closed flammable pipes from 55mm to 160mm diameter and can be face fixed to a wall or ceiling structure.
- Prevents the passage of fire and hot gases through concrete and masonry constructions
- Soil, waste and drainage ‘above ground’ applications
- Suitable for plasterboard partitions (PPC25 - PPC160 (400 series) only)
- Fire resistance of up to 120 minutes (200 series), 240 minutes (400 series)
- Galvanised steel outer casing (200 series)/Stainless steel outer casing (400 series)
- Tab closing device - easy to fix in place around pipe and rotate or slide into position
- Intumescent material is totally unaffected by water - robust, ‘non-flaking’ and difficult to tear
- CERTIFIRE Certificate No. CF635
- EC Certificate of conformity 1121 - CPD - JA5002
- Note: some sizes are temporarily unavailable - please see below for more information
Ref | Item | Availability |
---|---|---|
COL55-2H | PYROPLEX 2 hour pipe collar 55mm | In Stock |
COL82-2H | PYROPLEX 2 hour pipe collar 82mm | In Stock |
COL110-2H | PYROPLEX 2 hour pipe collar 110mm | In Stock |
COL160-2H | PYROPLEX 2 hour pipe collar 160mm | In Stock |
COL025-4H | PYROPLEX 4 hour pipe collar 25mm | Special Order - 24 Working Day Lead Time |
COL032-4H | PYROPLEX 4 hour pipe collar 32mm | Special Order - 24 Working Day Lead Time |
COL040-4H | PYROPLEX 4 hour pipe collar 40mm | Special Order - 24 Working Day Lead Time |
COL048-4H | PYROPLEX 4 hour pipe collar 48mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL055-4H | PYROPLEX 4 hour pipe collar 55mm | In Stock |
COL068-4H | PYROPLEX 4 hour pipe collar 68mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL082-4H | PYROPLEX 4 hour pipe collar 82mm | In Stock |
COL090-4H | PYROPLEX 4 hour pipe collar 90mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL110-4H | PYROPLEX 4 hour pipe collar 110mm | In Stock |
COL125-4H | PYROPLEX 4 hour pipe collar 125mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL135-4H | PYROPLEX 4 hour pipe collar 135mm | Special Order - 24 Working Day Lead Time |
COL160-4H | PYROPLEX 4 hour pipe collar 160mm | In Stock |
COL200-4H | PYROPLEX 4 hour pipe collar 200mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL225-4H | PYROPLEX 4 hour pipe collar 225mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL250-4H | PYROPLEX 4 hour pipe collar 250mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL315-4H | PYROPLEX 4 hour pipe collar 315mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL350-4H | PYROPLEX 4 hour pipe collar 350mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
COL400-4H | PYROPLEX 4 hour pipe collar 400mm | Temporarily unavailable Special Order - 24 Working Day Lead Time |
Pyroplex Pipe Collars have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. They will seal closed flammable pipes from 55mm to 160mm diameter and can be face fixed to a wall or ceiling structure.
The tab closing device means collars are easy to fix in place around pipe and rotate or slide into position - intumescent material is totally unaffected by water, is robust, ‘non-flaking’ and difficult to tear.
Specifically designed to prevent the passage of fire and hot gases through:
- Concrete and masonry constructions
- Suitable for plasterboard partitions (PPC25 - PPC160 (400 series) only)
- Soil, waste and drainage ‘above ground’ applications
Tested to BS 476: Part 20: 1987 and BS EN 1366-3: 2009 and has a European classification in accordance with BS EN 13501-2: 2007. Compliant with the requirements given in CERTIFIRE TS03.
- CERTIFIRE Certificate No. CF635
- EC Certificate of conformity 1121 - CPD - JA5002
Quick Links - Click To Jump To Section:
- Features & Benefits
- Ordering References
- 200 Series Pipe Collars
- 400 Series Pipe Collars CE Marked - Range for concrete and masonry walls and floors
- 400 Series Pipe Collars CE Marked - Range for plasterboard partitioning walls
- Installation Instructions
- Quality Approval
Features & Benefits
- Re-instates the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes
- Prevents the passage of fire and hot gases through concrete and masonry constructions
- Soil, waste and drainage ‘above ground’ applications
- Suitable for plasterboard partitions (PPC25 - PPC160 (400 series) only)
- Fire resistance of up to 120 minutes (200 series), 240 minutes (400 series)
- Seal closed flammable pipes from 55mm to 160mm diameter
- Can be face fixed to a wall or ceiling structure
- 200 series collar has a galvanised steel outer casing
- 400 series collar has a stainless steel outer casing
- Tab closing device - easy to fix in place around pipe and rotate or slide into position
- Intumescent material is totally unaffected by water - robust, ‘non-flaking’ and difficult to tear
- CERTIFIRE Certificate No. CF635
- EC Certificate of conformity 1121 - CPD - JA5002
Ordering References
200 Series Pipe Collars - 2 hour FR pipe collar with zintec mild steel galvanised coating
Order Ref | Part no. | Pipe Ø [mm] | Collar depth [mm] | No. of fixing lugs |
---|---|---|---|---|
COL55-2H | PPC55-2 | 55 | 60 | 3 |
COL82-2H | PPC82-2 | 82 | 60 | 3 |
COL110-2H | PPC110-2 | 110 | 60 | 4 |
COL160-2H | PPC160-2 | 160 | 60 | 6 |
400 Series Pipe Collars CE Marked - Range for concrete and masonry walls and floors
Stainless steel outer casing, Pyroplex graphite
Orientation and construction | ||||||||
---|---|---|---|---|---|---|---|---|
Order Ref | Part no. | Pipe Materials | Pipe Ø [mm] | Pipe wall thickness [mm] | Collar depth [mm] | No. of fixing lugs | Wall | Floor |
COL025-4H | PPC25-4 | PVC-u | 25 | 1.8 | 60 | 2 | EI 180 | EI 180 |
COL032-4H | PPC32-4 | PVC-u | 32 | 1.8 | 60 | 2 | EI 180 | EI 180 |
COL040-4H | PPC40-4 | PVC-u | 40 | 1.8 | 60 | 2 | EI 180 | EI 180 |
COL048-4H | PPC48-4 | PVC-u | 48 | 3.2 | 60 | 2 | EI 180 | EI 180 |
COL055-4H | PPC55-4 | PVC-u | 55 | 3.2 | 60 | 3 | EI 180 | EI 180 |
COL068-4H | PPC68-4 | PVC-u | 68 | 3.2 | 60 | 3 | EI 180 | EI 180 |
COL082-4H | PPC82-4 | PVC-u | 82 | 3.2 | 60 | 3 | EI 180 | EI 180 |
COL090-4H | PPC90-4 | PVC-u | 90 | 3.2 | 60 | 4 | E 180 & EI 180 | E 180 & EI 180 |
COL110-4H | PPC110-4 | PVC-u | 110 | 3.2 | 60 | 4 | EI 180 | EI 180 |
COL125-4H | PPC125-4 | PVC-u | 125 | 3.2 | 60 | 4 | EI 180 | EI 180 |
COL135-4H | PPC135-4 | PVC-u | 135 | 3.2 | 60 | 4 | EI 180 | EI 180 |
COL160-4H | PPC160-4 | PVC-u | 160 | 3.2 | 60 | 6 | EI 180 | EI 180 |
COL200-4H | PPC200-4 | PVC-u | 200 | 5.4 | 180 | 8 | EI 240 | EI 180 |
COL225-4H | PPC225-4 | PVC-u | 225 | 7.2 | 180 | 8 | EI 240 | EI 180 |
COL250-4H | PPC250-4 | PVC-u | 250 | 7.2 | 180 | 9 | EI 240 | EI 180 |
COL315-4H | PPC315-4 | PVC-u | 315 | 8.2 | 180 | 11 | EI 180 | EI 120 |
COL350-4H | PPC350-4 | PVC-u | 350 | 9.8 | 180 | 12 | EI 120 | EI 180* |
COL400-4H | PPC400-4 | PVC-u | 400 | 9.8 | 180 | 13 | EI 120 | EI 180* |
*PPC350 and PPC400 achieve EI 180 only, when installed on both sides of the separating element (i.e floor)
400 Series Pipe Collars CE Marked - Range for plasterboard partitioning walls
Stainless steel outer casing, Pyroplex graphite
Orientation and construction | |||||||
---|---|---|---|---|---|---|---|
Order Ref | Part no. | Pipe Materials | Pipe Ø [mm] | Pipe wall thickness [mm] | Collar depth [mm] | No. of fixing lugs | Plasterboard Wall |
COL025-4H | PPC25-4 | PVC-u | 25 | 1.9 - 3 | 60 | 2 | EI120 |
PPC25-4 | PE | 25 | 2.4 - 3.7 | 60 | 2 | EI120 | |
PPC25-4 | PP | 25 | 1.8 - 3.7 | 60 | 2 | EI90 & E120 | |
COL032-4H | PPC32-4 | PVC-u | 32 | 1.9 - 3 | 60 | 2 | EI120 |
PPC32-4 | PE | 32 | 2.4 - 3.7 | 60 | 2 | EI120 | |
PPC32-4 | PP | 32 | 1.8 - 3.7 | 60 | 2 | EI90 & E120 | |
COL040-4H | PPC40-4 | PVC-u | 40 | 1.9 - 3 | 60 | 2 | EI120 |
PPC40-4 | PE | 40 | 2.4 - 3.7 | 60 | 2 | EI120 | |
PPC40-4 | PP | 40 | 1.8 - 3.7 | 60 | 2 | EI90 & E120 | |
COL048-4H | PPC48-4 | PVC-u | 48 | 2.2 - 3.4 | 60 | 2 | EI120 |
PPC48-4 | PE | 48 | 2.5 - 4 | 60 | 2 | EI120 | |
PPC48-4 | PP | 48 | 1.9 - 4.4 | 60 | 2 | EI90 & E120 | |
COL055-4H | PPC55-4 | PVC-u | 55 | 3.3 - 5.2 | 60 | 3 | EI120 |
PPC55-4 | PE | 55 | 3.3 - 5.2 | 60 | 3 | EI120 | |
PPC55-4 | PP | 55 | 2.3 - 7.5 | 60 | 3 | EI90 & E120 | |
COL068-4H | PPC68-4 | PVC-u | 68 | 3.3 - 5.2 | 60 | 3 | EI120 |
PPC68-4 | PE | 68 | 3 - 5.4 | 60 | 3 | EI120 | |
PPC68-4 | PP | 68 | 2.3 - 7.5 | 60 | 3 | EI90 & E120 | |
COL082-4H | PPC82-4 | PVC-u | 82 | 3.3 - 5.2 | 60 | 3 | EI120 |
PPC82-4 | PE | 82 | 3 - 5.4 | 60 | 3 | EI120 | |
PPC82-4 | PP | 82 | 2.3 - 7.5 | 60 | 3 | EI90 & E120 | |
COL090-4H | PPC90-4 | PVC-u | 90 | 4.8 - 7.4 | 60 | 4 | E120 |
PPC90-4 | PE | 90 | 3.4 - 6.6 | 60 | 4 | EI120 | |
PPC90-4 | PP | 90 | 2.7 - 10 | 60 | 4 | EI120 | |
COL110-4H | PPC110-4 | PVC-u | 110 | 4.8 - 7.4 | 60 | 4 | EI120 |
PPC110-4 | PE | 110 | 3.4 - 6.6 | 60 | 4 | EI120 | |
PPC110-4 | PP | 110 | 2.7 - 10 | 60 | 4 | EI120 | |
COL125-4H | PPC125-4 | PVC-u | 125 | 4.8 - 7.4 | 60 | 4 | EI120 |
COL160-4H | PPC160-4 | PVC-u | 160 | 6.2 - 9.5 | 60 | 6 | EI120 |
PPC160-4 | PE | 160 | 4.9 - 9.1 | 60 | 6 | EI120 | |
PPC160-4 | PP | 160 | 4 - 9.1 | 60 | 6 | EI120 |
Installation Instructions
- Ensure substrate around pipe is flat and free from obstructions – if necessary make good by using Pyroplex® Intumescent Acrylic Sealant.
- Release retaining pin and position pipe collar around pipe.
- Slide tab through slot in pipe collar and fold back 180˚ to secure.
- Secure pipe collar by drilling holes in structure by using fixing lugs as template. To fix use M8 x 65mm sleeve anchors or 50mm [minimum] expanding bolts. Do not use plastic raw plugs and or plastic sleeve anchors.
- When the collar has been securely fitted into place any residual gaps between the collar and the substrate can be filled using Pyroplex® Intumescent Acrylic Sealant.
Flexible Partition Walls - 400 series only
- Ensure substrate around pipe is flat and free from obstructions – if necessary make good by using Pyroplex® Intumescent Acrylic Sealant around the perimeter.
- Release retaining pin and position pipe collar around pipe.
- Slide tab through slot in pipe collar and fold back 180˚ to secure.
- Secure pipe collar by drilling holes in structure and using fixing lugs as template. To fix use M8 continuous all thread bar and secure either side with appropriate size nut.
- When the collar has been securely fitted into place any residual gaps between the collar and the substrate can be filled using Pyroplex® Intumescent Acrylic Sealant.
Typical Installation - wall application
Quality Approval
Pyroplex Limited has a Quality Management System that meets the requirements of ISO 9001, and is independently verified by BSI Quality Assurance under Certificate No. FM10371.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Data sheet
- Level of Protection
- Up to 4 hours
- Product Usage Type
- Fire Collar
- Product Range
- Pyroplex
- Fire Rating
- 120 Minutes
- Fire Rating
- 240 Minutes
Questions
Question about the product
Be the first to ask a question about this product!
IMPORTANT SHIPPING & DELIVERY INFORMATION
Pyroplex Pipe Collars is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT
Pyroplex Slimline Pipe Collar (200 Series)
Specifically designed to reinstate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. The collars will seal closed flammable pipes from a 55mm to 160mm diameter and can be face fixed to a wall or ceiling structures. Fire resistance of up to 120 minutes...
Pyroplex Fire Rated Silicone Sealant
1 part, low modulus, neutral cure, halogen-free product suitable for the sealing of construction joints, and around pipe penetrations which have been protected by the recommended Pyroplex intumescent product. Ideal for the weathersealing of curtain walling, building facades and expansion joints in fire rated walls. Fire resistance up to...