Follow us on:

Pyroplex Slimline Pipe Collar (200 Series) | Up To 120 Minutes Fire Resistance

Pyroplex Slimline Pipe Collar (200 Series)

NOR4975
NOR4975

Specifically designed to reinstate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. The collars will seal closed flammable pipes from a 55mm to 160mm diameter and can be face fixed to a wall or ceiling structures.

  • Fire resistance of up to 120 minutes
  • Zintec coated steel outer casing
  • Embossed for identification and traceability purposes
  • Tab closing device means the collars are easy to fix in place around the pipe androtate or slide into position
  • Intumescent material is totally unaffected by water, is robust, ‘non-flaking’ and difficult to tear
  • Suitable for use on concrete, masonry and plasterboard partitions

Please Note: This Product is Made To Order subject to a MOQ (see below) and an extended lead time

Item
£7.78(incl. VAT)
£6.48(ex. VAT)
Quantity
Please choose your colour
The Product may be Subject to Extended Lead Times

The minimum purchase order quantity for the product is 100.

questions 1 question about the product
Description

Pyroplex 200 Series Slimline Pipe Collars have been specifically designed to reinstate the fire resistance of a wall or floor which has been penetrated by plastic flammable pipes used in soil, waste and drainage services. The collars will seal closed flammable pipes from a 55mm to 160mm diameter and can be face fixed to a wall or ceiling structures, suitable for use on concrete, masonry and plasterboard partitions.

Tested in accordance with EN1366-3, achieving a fire resistance period of up to 120 minutes (depending upon the application), classified in accordance with EN13501-2: 2007, classification report No. 412471. ETA is issued in accordance with (EU)No.305/2011 based upon EAD350454-00-1104 - ETA 19/0440

Pyroplex 200 Series SL Pipe Collars have been specifically designed to prevent the passage of fire and hot gases through:

  • Concrete and masonry constructions - Suitable for plasterboard partitions 55mm to 160mm
  • Soil, waste and drainage ‘above ground’ applications
  • Suitable for plastic flammable pipes with PVC-C, PVC-U, PE, PP, ABS and SAN+PVC pipes



Quick Links - Click To Jump To Section:




Features & Benefits


  • Pyroplex 200 Series SL Pipe Collars have achieved a fire resistance of up to 120 minutes
  • Pyroplex 200 Series SL Pipe Collars have a zintec coated steel outer casing
  • Embossed for identification and traceability purposes
  • Tab closing device means the collars are easy to fix in place around the pipe androtate or slide into position
  • Intumescent material is totally unaffected by water, is robust, ‘non-flaking’ and difficult to tear
  • Reinstate the fire resistance of walls or floors penetrated by plastic flammable pipes used in soil, waste and drainage services
  • Seal closed flammable pipes from a 55mm to 160mm diameter
  • Can be face fixed to a wall or ceiling structures
  • Suitable for use on concrete, masonry and plasterboard partitions



Installation Instructions


Masonry Wall and Floor Constructions

Further information on the general supporting construction, pipe diameters and pipe wall thicknesses can be referenced in the Declaration of Performance

  1. Ensure the substrate around the pipe is flat and free from obstructions – if necessary make good by using Pyroplex CE Intumescent Acrylic Sealant around the perimeter.
  2. Release the retaining pin and position the pipe collar around the pipe.
  3. Slide the tab through the slot in the pipe collar and fold back 180˚ to secure.
  4. Secure the pipe collar by drillingholes in the structure by using fixing lugs as a template. To fix,use metal sleeve anchor M6 x 65s or CE marked alternative anchors. Do not use plastic raw plugs and/or plastic sleeve anchors.
  5. When the collar has been securely fitted into place, any residual gaps between the collar and the substrate can be filled using Pyroplex CE Intumescent Acrylic Sealant.

 

Flexible Partition Walls

Flexible partitions - fully insulated or insulated partitions. Refer to Declaration of Performance which define the field of application for the supporting construction.

  1. Ensure the substrate around the pipe is flat and free from obstructions – if necessary, make good by using Pyroplex CE Intumescent Acrylic Sealant around the perimeter.
  2. Release the retaining pin and position the pipe collar around the pipe.
  3. Slide the tab through the slot in the pipe collar andfold back 180˚ to secure.
  4. Secure the pipe collar by drilling holes in the structureand using fixing lugs as a template. To fix,use Fishcer HM 6 x 65s or CE marked alternative anchors.
  5. When the collar has been securely fitted into place, any residual gaps between the collar and the substrate can be filled usingPyroplex CE Intumescent Acrylic Sealant.

 

Typical Installation - wall application - Masonry wall construction



Quality Approval


Pyroplex Limited have a Quality Management System that meets the requirements of ISO 9001 and an Environmental Management System that meets the requirements of ISO 14001, both are independently verified by BSI Quality Assurance under Certificate Numbers FM10371 and EMS 637894. Copies of these certificates are available to download from the data sheets tab further above.



Ordering References


Part No./Order reference Pipe Diameter (mm) Collar Depth [mm] No. of Fixing Lugs
PPC55-SL (MOQ 100) 55 30 3
PPC75-SL (MOQ 75) 75 30 4
PPC82-SL (MOQ 75) 82 30 4
PPC110-SL (MOQ 100) 110 30 5
PPC160-SL (MOQ 48) 160 45 6



Field of Application


Table 1 - UPVC pipe – Flexible and Rigid Wall [100mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed both sides of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 2.30 - 3.70 PPC55-2SL EI 90 - U/C, EI 120 - U/C
75 3.20 - 4.90 PPC75-2SL  
82 3.40 - 5.20 PPC82-2SL  
110 4.20 - 6.60 PPC110-2SL  
160 6.20 - 9.50 PPC160-2SL EI 120 - U/C

 

Table 2 - Polypropylene pipes – Flexible and Rigid Wall [100mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed both sides of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 2.90 - 6.90 PPC55-2SL EI 90 - U/C, EI 120 - U/C
75 3.20 - 10.30 PPC75-2SL  
82 2.40 - 11.30 PPC82-2SL  
110 2.70 - 15.10 PPC110-2SL EI90 - U/C, E 120 - U/C
160 4.00 - 21.90 PPC160-2SL

 

Table 3 - Polyethylene pipes – Flexible and Rigid Wall [100mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed both sides of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 3.00 - 4.60 PPC55-2SL EI 120 - U/C
75 2.90 - 6.90 PPC75-2SL  
82 2.40 - 11.30 PPC82-2SL  
110 2.80 - 7.50 PPC110-2SL  
160 4.00 - 14.60 PPC160-2SL EI90 - U/C, E 120 - U/C

 

Table 4 - UPVC pipe – Rigid Floor [150mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed to the underside of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 2.30 - 3.70 PPC55-2SL EI 120 - U/C
75 3.20 - 4.90 PPC75-2SL  
82 3.40 - 5.20 PPC82-2SL  
110 4.20 - 6.60 PPC110-2SL  
160 6.20 - 9.50 PPC160-2SL EI 120 - U/C

 

Table 5 - Polypropylene pipes – Rigid Floor [150mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed to the underside of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 2.90 - 6.90 PPC55-2SL EI 120 - U/C
75 3.20 - 10.30 PPC75-2SL  
82 2.40 - 11.30 PPC82-2SL  
110 2.70 - 15.10 PPC110-2SL  
160 4.00 - 21.90 PPC160-2SL EI 120 - U/C

 

Table 6 - Polyethylene pipes – Rigid Floor [150mm minimum thickness]

Pyroplex 200 Series SL Pipe Collars to be installed to the underside of the supporting construction

Pipe Diameter (mm) Pipe thickness (mm) Collar Type Classification
55 3.00 - 4.60 PPC55-2SL EI 120 - U/C
75 2.90 - 6.90 PPC75-2SL  
82 2.40 - 11.30 PPC82-2SL  
110 2.80 - 7.50 PPC110-2SL  
160 4.00 - 14.60 PPC160-2SL EI90 - U/C

 

IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.

Product Details
4975-802806

Data sheet

Key Features
Fire resistance of up to 120 minutes
Product Usage Type
Fire Collar
Product Range
Pyroplex
Fire Rating
90 Minutes
Fire Rating
120 Minutes
Attachments
Download


Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.

Questions

Question about the product

* Required fields
(read)
questions Oliver Hunt on 2023-08-04 12:32:31
Question: 

Do you sell in 50 quantity rather than 100 please?

Answer from Rawlins’ Technical Team:

Unfortunately no.

The minimum order quantity for this product is 100 units.

IMPORTANT SHIPPING & DELIVERY INFORMATION

Pyroplex Slimline Pipe Collar (200 Series) is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.

Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.

Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.

All delivery costs below are excluding VAT